Asenware Addressable Fire Alarm Heat Detector

Art.Nr.:
GCT10405

Call for Price

01847213868

- LPCB Approved

- It can realize electronic coding and rewrite the address via coder in situ.

- Within a single-chip microcomputer, it can realize real-time data acquisition and processing, realize a curve tracing for the field situation.
- It has a temperature compensation function and a sensor fault detection function (fault reporting to fire alarm control panel).

- Built-in remote indicator output terminal, drive remote indicator lit when fire alarm

Brand : ASENWARE

Model : AW-D302

Country of Origin: UK 

 

AW-D302 Addressable Heat Detector (Detector hereunder) is a mated product of the AW-FP300 fire alarm control panel. It uses a two-bus work mode. With an internal microprocessor, it supports electronic coding. The detector realizes real-time acquisition of the in situ temperature data and sends back the data to a fire alarm control panel. It can also receive and execute the control commands given by a fire alarm control panel. When in a routine inspection, the detector indicator will blink. When there is a fire in the monitored area and the temperature has reached the alarm threshold, the fire alarm control panel will confirm a fire alarm according to the received message sent from the detector, and the detector indicator will light at the same time to indicate a fire alarm.

The detector is suitable for such industrial and civil buildings that have a great deal of heat when fire takes place, such as kitchens, boiler rooms, generator rooms, drying workshops and smoking rooms and is not suitable for places with a great deal of smoke but little heat.

 

Technical Specifications:

Operating Voltage

Loop 24V(18V~28V)

Standby Current

<0.3mA

Alarm Current

<1.5mA (without remote indicator)
<3.5mA (with remote indicator)

Class

A2

Fire LED

Red, Flash in polling, and illuminate in alarming.

Remote indicator output

Polarity-sensitive output, directly connect to remote indicator (built in 10k resistor in series, max. output current is 2mA); The red indicator will blink in
the monitoring status or remain lit in the alarm status.

Programming

Electronically addressed.

Programming Range

Occupying one address within 1~324.

Wiring

Loop: two wire, polarity-insensitive

Environmental Temperature

-10℃~+50℃

Relative Humidity

≤95%, non-condensing

Material of Enclosure

ABS

Dimension

Diameter: 100mm
Height: 60mm(with the base)

Mounting Hole Distance

44.5mm~64.3mm

Weight

About 115g(with the base)

Certificate

CE, LPCB  

 

Write Your Own Review
You're reviewing:Asenware Addressable Fire Alarm Heat Detector
Your Rating