Brand : Bosch
Model : FPA-5000-01
Country of Origin: GERMANY
Features:
- Modular configuration allowing for easy extension
- Interconnection of up to 32 Panel Controllers,
- Remote Keypads, and OPC servers
- Multiple CAN loop connection with highperformance
- Ethernet backbone and redundancy
- Installation and auto-detection of functional
- modules by simply plugging them into the panel rail
- Connection to BIS Building Integration System via
- OPC server
Thanks to the modular configuration, the innovative
FPA‑5000 Modular Fire Panel easily adapts to local
circumstances and regulations. Due to the different
functional modules, country-specific characteristics
are accommodated in the connection just as quickly as
the respective alarm handling.
The fire panel is available with two different housings:
• Housing for mounting directly on the wall
• Frame installation housings which are fitted to the
mounting frame and can be swiveled.
With the aid of special mounting kits, the housings can
be mounted in 482.6 mm (19") cabinets. All housings
can be extended with various additional housings for
all conceivable applications.
The FMR‑5000 Remote Keypad offers the decentralized
operation of a control panel or control panel network.
Thanks to the external CAN and Ethernet interfaces,
several Panel Controllers and Remote Keypads can be
interconnected. Using either a single‑loop structure or
multiple‑loop structures with Ethernet backbone, the
network can be adapted to nearly every application
conditions.
CAN/Ethernet Network
1 Fire panel
2 Remote Keypad
Additionally, the Ethernet interfaces allow the
connection to: Building Management System BIS,
Voice Alarm System Praesideo/PAVIRO, Remote
Services, FSM-2500/FSM-5000 Fire Monitoring
System.
FPA-5000 systems can be connected to the Bosch
UGM Universal Security System and thus, be
integrated into a large network system.
The entire fire detection system is configured via a
laptop using the FSP-5000-RPS Programming
Software.
Operation / processing of messages
The operation and the processing of all messages are
easy and intuitive thanks to the ergonomicallydesigned
control panel with its TFT touch‑screen
offering a menu-driven handling and multi-color
display. To that end, there are permanently located
keys on the right, bottom, and upper edge of the
display as well as variably located virtual keys in the
touch-screen area.
Modular Structure
Due to its modular structure, the FPA-5000 Modular
Fire Panel provides complete flexibility and thus
customized solutions for any application.
Depending on the requirements, the following
selection can be made when planning:
1. Housing type: Frame installation or wall-mount
– Selection of a basic housing
– Optional Extension Housings
– Optional Power Supply Housings
– Optional kits for installation in 48 cm (19'') racks
2. Operating and Display Unit with Panel Controller
– Selection from the various language variants
3. Panel Rail
– Selection according to housing type and/or
number of required functional modules
4. Functional modules
– Selection based on planning and country-specific
requirements
5. Power supply
– Batteries
– Additional power supply facilities
– Power Supply Brackets are preinstalled ex-works
for Frame Installation Housings
– For Wall-mount Housings, Power Supply Brackets
are selected as needed
6. Additional accessories
– Front Doors
– Printer with Frame Installation Housing
– Cable Sets for special applications
Modules
The functional modules are autonomous, encapsulated
units that can be inserted into any control panel slot
using plug-and-play technology. Thus, the power
supply and the data traffic to the control panel are
indicated automatically without any additional
settings. The module is automatically identified by the
control panel and functions in the default operating
mode.
Wiring to external components is performed using
compact connector/screw terminals.
After a replacement, only the connectors need to be
reinserted; extensive rewiring is no longer required.
Detection Points
The Address Cards activate detection points. The
FPA-5000 governs up to 4096 detection points.
Each element and input which is able to set off an
alarm requires a detection point.
Inputs are considered as detection points if they are
programmed accordingly in the FSP-5000-RPS
Programming Software.