AW-D314 loop isolator (hereinafter referred to as AW-D314), mainly used to isolate a portion of a short circuit on the bus, other devices on the bus to ensure normal operation. Upon elimination of the short circuit fault, AW-D314 can be isolated out their own part back into the system. It is worth noting: AW-D314 using the bus to facilitate the determination of the location of a short circuit.

 

Technical Specifications: 

 

Nominal Line Voltage ( VNOM)

24V

Standby Current

<3mA

Capacity

32 devices

Indicate

Yellow (flashes when polling, illuminates in action.)

Maximum Line Voltage ( VMAX)

28V

Minimum Line Voltage ( VMIN)

16V

Maximum voltage at which the device isolates ( VSOMAX)

11V

Minimum voltage at which the device isolates ( VSOMIN)

8V

Maximum voltage at which the device reconnects( VSC MAX)

4V

Minimum voltage at which the device reconnects( VSC MIN)

1.4V

Maximum rated continuous current with the switch closed ( IC MAX)

1A

Maximum rated switching current ( IS MAX)

3A

Maximum leakage current with the switch open ( ILMAX)

15mA

Maximum series impedance with the switch closed( ZC MAX)

0.15Ω

Operating Temperature

-10℃~+55℃