Asenware Addressable Fire Alarm System Input Output Module

Art.Nr.:
GCT10409

Call for Price

01847213868

- LPCB Approved

- Executive standard: EN54-18

- Operation voltage: loop DC24V (polarity-insensitive);power DC24V(polarity-insensitive)

- Quiescent current: loop current<0.8mA; power current<2mA

- Action current: loop current<5mA; power current<15mA

- Capacity of the output control contact: 1A@DC30V

Brand : ASENWARE  

Model : AW-D319

Country of Origin: UK 

The AW-D319 Addressable I/O Module (AW-D319 for short) is used with AW-FP300 fire alarm control panel. It is mainly used to realize an output control for fire linkage equipment (such as smoke dampers, blow valves and fire dampers) and receive the feedback signals of the fire linkage equipment so that a judgment on whether or not the fire linkage equipment is operating normally can be done.

 

Technical Specifications: 

 


Operating Voltage

Signal Loop 24V(18V~28V)
Power 24VDC(20VDC~28VDC)

Standby Current

Loop<0.8mA ; Power<2mA

Action Current

Loop<5mA ; Power<15mA

Output Capacity

1A@DC30V

Input Mode Setting

NC or NO input mode can be set by the jumper JP4.

Programming Method

Electronically addressed

Code Range

One address within 1~324.

 
Indicators

Inspection indicator: l blink once about every 12 seconds in the inspection status or remain lit in the output status;
Input indicator : remain lit in the feedback status.

Operating Temperature

-10℃~+55℃

Relative Humidity

≤95% , non-condensing

Material of Enclosure

ABS

 
Dimension (L×W×H)

86mm×86mm×41mm
(with base)

Mounting Hole Distance

60.5mm

Weight

About 148g (with base)