Asenware Addressable 01 Loop Fire Alarm Control Panel

Art.Nr.:
GCT10401

Call for Price

01847213868

- LPCB Approved Product
- 4.3'' color-screen LCD
- Up to 324 addresses per loop
- Record capacity of 1000 historical events
- Integral printer
- U-disk interface for save of configuration
- Anti-tamper protection by a key lock
- Connection with up to 30 fire indicating panels

Brand : ASENWARE

Model : AW-FP300

Country of Origin: UK  


the purpose of the AW-FP300 Fire Alarm Control Panel (FACP) is to monitor input signals, give indications and possibly activate outputs as programmed. It is designed to comply with EN 54-2 with qualities of simple installation, operation and easy maintenance. The AW-FP300 panel is an addressable fire detection panel with 1 loop of 324 addressable points and expansion capabilities. It is compatible with other peripherals made by ASENWARE with its own protocol.

 

Technical Specification:  

 Power supply 

Mains supply 

230VAC (-15%, +10%). 47 ~ 63Hz. Max current 0.8A 

Mains fuse 

T3.15AL250V 

Operating voltage 

18.5 ~ 30VDC 

Recommended mains cable 

Screened or standard/black mains cable, cable size 0.75mm2 

Power rating 

Imax.a=1.2A; Imax.b=2.6A; Imin=0.65A 

Max. charging current 

1.2A 

Max. battery supply current 

4A (when the Mains is disconnected) 

Battery capacity, type and recommended model 

Max. capacity 2×12V/17Ah; Min. capacity 2×12V/12Ah 
VRLA. PS-12170 for 17Ah (Power-sonic), PS12120 for 12Ah (Power-sonic) 

Max. internal resistance of battery 

1.5Ω

Battery fuse 

F8AL250V 

Recommended battery cable 

14AWG 

Quiescent current (full loaded) 

< 0.4A 

Outputs 

S.C. Out (+, -) 

Output voltage 

18.5 ~ 30VDC 

Max. output current 

0.5A 

Fuse rating 

F1AL250V 

End of line resistor 

4K7 

Recommended type of cable 

Plain unscreened cable, 1.5mm2 

Cable diameter 

1mm2 ~2mm2 

Transmission distance 

≤1500m 

Max. number of sounders @50mA 

20 

F.P.E. Out (+, -) 
F.A. Out (+, -) 

Output voltage 

18.5 ~ 30VDC 

Max. output current 

0.5A 

Fuse rating 

F1AL250V 

End of line resistor 

4K7 

Recommended type of cable 

Plain unscreened cable, 1.5mm2 

Cable diameter 

1mm2 ~2mm2 

Transmission distance 

≤1500m 

Fault Out 
(NC, COM, NO) 

Contact capacity 

30VDC@2A, 125VAC@0.5A 

Recommended type of cable 

Plain unscreened cable, 1.5mm2 

Cable diameter 

1mm2 ~ 2mm2 

24VK (+, -) 

Output voltage 

18.5 ~ 30VDC 

Max. output current 

0.6A 

Fuse rating 

F1AL250V 

Recommended type of cable 

Plain unscreened cable, 1.5mm2 

Cable diameter 

1mm2 ~2mm2 

Input 

Class change (+, -) 

Input mode 

Passive 

Cable resistance 

≤500Ω

Recommended type of cable 

Plain unscreened cable, 1.5mm2 

Cable diameter 

1mm2 ~2mm2 

Loop 

Loop Out (+, -) 
Loop In (+, -) 

Output voltage 

16.5 ~ 30VDC, pulse 

Output current 

0 ~0.3A 

Loop type 

Class A 

Recommended type of cable 

Screened or unscreened twisted-pair, 1.5mm2 

Transmission distance 

≤1000m 

Cable diameter 

1mm2 ~2mm2 

Network communication 

RS-485 

Max. number of FIPs 

30 

Transmission rate 

9600 bps 

Recommended type of cable 

Screened or unscreened twisted-pair, 1mm2 

Transmission distance 

≤1000m 

Cable diameter 

1mm2 ~5mm2 

CAN 

Max. number of panels 

20 

Transmission rate 

Optional: 10K, 20K, 50K and 100K bps 

Recommended type of cable 

Screened or unscreened twisted-pair, 1mm2 

Transmission distance 

≤1000m 

Cable diameter 

1mm2 ~5mm2 

Physical dimensions 

Approx. Dimensions of the panel (W×H×D) 

430×560×170mm 

Approx. weight (without battery) 

14kg 

Operating conditions 

Temperature range: 0°C~45°C; Max relative humidity: 95% (40°C ±2°C, no condensation) 

Write Your Own Review
You're reviewing:Asenware Addressable 01 Loop Fire Alarm Control Panel